Most hospitals already have a standby diesel set and a UPS layer, so a mobile unit is not "power from zero" — it covers the gap when the fixed set fails, goes into overhaul, runs out of fuel, or while a new wing is still being commissioned. Once you fix that role, the rating stops being a multiple of the transformer size, and the connection point stops being a guess.

Short answer: a 400–600 bed general hospital needs a 200–500 kW mobile unit to carry theatres, ICU, blood bank, medical lifts and fire loads — not a unit sized on a 1,250 kVA transformer. The number that matters is the actual kW of critical + fire load, typically 25–35% of installed capacity. Uninterrupted power for theatres and ICU is the UPS's job; the vehicle takes over once the battery string has done its part.

Yellow pickup-mounted emergency power unit parked on a city street beside high-rise buildings
City standby: a pickup-mounted unit at the kerb, feeding a spare breaker in the LV room. On urban hospital sites, body length and turning circle usually bite before the rating does — a 2.2 m basement clearance rules out most power vehicles.

Divide the load into tiers before talking about kW

Hospital distribution is already prioritised. The vehicle does not carry the campus; it carries the part that cannot stop. In practice that means three decisions: what to carry, for how long, and who closes the switch.

Load tierTypical equipmentShare of loadAllowed interruptionVehicle carries?
VitalTheatres, ICU/NICU, delivery, blood bank, DSA, network room20–30%0 (UPS / isolation supply)Yes, after the battery string
FireFire pumps, sprinkler, smoke extract, fire lifts, escape lighting10–15%≤15 sYes, first priority
EssentialMedical lifts, laboratory, imaging, oxygen plant, water pumps20–25%≤30 sDepending on capacity
GeneralHVAC, lighting, kitchen, laundry, offices35–45%1–2 h acceptableNormally no

The important use of this table is to strip general load before sizing. A campus quoted at "2,000 kW installed" often has half of it in chillers and lighting; sizing on that number costs an extra USD 100,000 and produces a vehicle that cannot get through the gate.

Sizing: bed-count and transformer rules both mislead

BedsTransformersCritical + fire loadRecommended unitConnection
200 (county)2 × 800 kVA180–250 kW200–250 kWSpare breaker, LV room
400 (city)2 × 1,250 kVA280–380 kW300–400 kWSpare breaker + rapid connection box
600 (tertiary)3 × 1,250 kVA400–520 kW400–500 kWRapid connection box (400/630 A)
800+2 × 1,600 kVA and up550–750 kW630–800 kW10 kV mobile substation or MV vehicle

One exception needs its own calculation: imaging. A 3.0 T MRI gradient coil can draw 3–4× its rated current during sequence switching, and CT tubes and linear accelerators behave in the same family. If the vehicle carries that load directly, size on steady state plus the step, and preferably keep the imager behind a UPS or its own feeder.

Connection: three ways, and only one avoids an outage

MethodWhat it involvesOutage neededWhen it fits
Spare breaker in LV roomCable onto a reserved breaker, open the bus coupler, feed one section5–15 minSpare way exists and a section can be dropped briefly
Rapid connection boxFixed 400/630 A socket on the wall, mechanically interlocked with mainsNone, connect in 10 minNew build or a hospital refurbished in the last five years
Mobile substation / MV unit10 kV into a spare ring-main way, step down to 400 V20–30 minAbove 800 kW, or no LV cable route

Switching time and UPS: who covers which minute

Theatre and ICU battery strings typically hold 15–30 minutes — enough for the fixed set to start and the ATS to transfer. If the fixed set does not start, a vehicle takes 40–90 minutes to arrive and connect in a city. The real risk is therefore not "do we have a vehicle", it is "does the battery string survive the gap".

Three practical consequences: recalculate UPS autonomy on the actual load (a five-year-old string often delivers only 60% of nameplate); install the connection point before you need it; and write "connect the mobile generator" into the hospital's emergency drill script as a formal step, not an improvisation.

Targets: fire loads ≤15 s, essential loads ≤30 s, theatres and ICU 0 s — the zero comes from the UPS, not from the generator. Any claim that a vehicle delivers "zero-transfer" power deserves the question "through what".

Harmonics, exhaust and noise: three hospital-specific constraints

Acceptance: three tests, all recorded

TestMethodPass criterion
Load testResistive load 100% for 2 h, then 110% for 1 hStable water, oil and exhaust temperature; no derate, no trip
Transfer drillAt least twice, one at night, with a real mains interruptionFire loads back within 15 s, essential within 30 s, UPS stays on inverter
Endurance and refuellingRun to low-fuel alarm at full load; practise a refuel≥8 h; refuel completed within 30 min

Questions hospitals actually ask

We already have a standby generator — why a vehicle?

Different failure. The fixed set answers "what if mains fails"; the vehicle answers "what if the fixed set fails" — breakdown, major overhaul, fuel contamination, or a capacity gap during expansion. Tertiary hospitals also use one for months while a new wing is commissioned.

Can the vehicle feed a theatre directly?

No. A theatre is protected by a UPS and an isolation transformer; the vehicle feeds the UPS input so the battery is not drained. A direct cable into a theatre is both non-compliant and destroys the IT-system insulation monitoring.

What size for a 400-bed hospital?

300–400 kW covers critical and fire loads. The precise figure comes from the hospital's load calculation and the size of the imaging department; we do not recommend sizing on transformer capacity.

Does connection require a mains outage?

With a rapid connection box, no — only the bus coupler is opened. Only the spare-breaker method needs a 5–15 minute outage, which is why fitting a connection box during construction is the best-value item in the project.

Can we park a fuel tank on site?

Rarely. Hospitals are assembly occupancies and temporary fuel storage needs fire approval. Eight hours on board plus a tanker outside the perimeter is the normal arrangement.

Will the noise reach the wards?

Yes, and it is the most common complaint. 65–70 dB(A) at 7 m against a 45 dB(A) night limit at a ward façade cannot be solved by insulation alone — position and barriers do the work.